Fire Protection of Steel Structures

Steel structures

Building regulations require certain elements of a structure to have fire resistance. Whether or not an element requires fire resistance depends on the size the building, what it will be used for and what the function of the element is.

When exposed to fire, all commonly used structural materials lose some of their mechanical strength. Heavily loaded steel will lose its designed safety margin at temperature around 550°C – regardless of the grade of steel. To protect the structural steel in your building, use PAROC fire protection slabs. Depending on the application, you can use one of three methods for fire protection: profile, box and solid.

The bigger volume of steel in the exposed area, the better fire resistance it has. How quickly the steel structure heats up in a fire can simply be described as the relation between the surface exposed to the fire and the steel volume of the profile. This relation is called the section factor A/V. A high section factor gives a quick temperature raise of the steel. In practice, this means that thin steel structures demand thicker protection.

Use tables 1 and 2 to find the fire class you need and the required product thickness for the most common steel profiles.

When the I profile has a height greater than 450 mm, install the insulation so that it matches the profile.

Insulation thickness for different beams, 3- and 4-sided fire exposure, critical temperature 450 °C

Fire class 
 R 30  R 60  R 90   R 120 
  Thickness of PAROC FPS 17 (mm)  Thickness of PAROC FPS 17 (mm)  Thickness of PAROC FPS 17 (mm)  Thickness of PAROC FPS 17 (mm) 
 Steel profile 3-sided fire exp.4-sided fire exp. Steel profile  3-sided fire exp.4-sided fire exp.  Steel profile 3-sided fire exp.4-sided fire exp. Steel profile  3-sided fire exp.4-sided fire exp.
 IPE 160 – 600 2020  IPE 330 – 600 2020 IPE 600 25 30 IPE 600 40 50 
   IPE 240 – 300   2025 IPE 500 30 40 IPE 550 50 50 
   IPE 160 – 220 25 30 IPE 360 – 450 40 40 IPE 450 – 500 50 60 
       IPE 220 – 33050 50 IPE 400 60 60 
      IPE 160 – 200 50 60 IPE 300 – 360 60 – 
 HE 100A – HE 600A20 20 HEA 180 – 600 20 20 HEA 600 20 20 HEA 360 – 600 40 40 
    HEA 100 – 160 2025 HEA 320 – 500 20  25 HEA 300 – 340 40 50 
       HEA 30020 30 HEA 240 – 280 40 60 
       HEA 200 – 280 3040 HEA 220 50 60 
       HEA 100 – 180 4050 HEA 200 50 – 
          HEA 100 – 180 60 –
 HE 100B – HE 600B 2020HEB 100 – 60020 20 HEB 320 – 600 20 20 HEB 300 – 600 30 40 
      HEB 220 – 300 2025HEB 240 – 280 40 40 
       HEB 20020 30 HEB 180 – 220 40 50 
      HEB 140 – 180 25 40 HEB 160 40 60 
      HEB 120 30 40 HEB 120 – 140 50 60 
      HEB 100 40 50 HEB 100 60 – 